Voltage measuring relay battery monitor 12V
The voltage measuring relay monitors the DC voltage applied to terminals A1 and A2.
The relay picks up when the voltage to be measured is below the set value V< (battery is empty)
and the set delay time 0-10 minutes has elapsed.
This condition is indicated by the yellow LED lighting up.
The relay returns to its rest position as soon as the voltage to be monitored exceeds the set value at v> (charging end voltage).
Technical data
-
Voltage supply:
- 12V: 10 - 15.5VDC
- Leistungsaufnahme : 0,8W
- Betriebsart: Continuous operation
-
Measuring range:
- Accuracy: 2% over total temperature and voltage range
- Repetitive Accuracy: +/- 2%
- Measuring range U :
- 12V: Undervoltage 10,5-12,5V / Overvoltage 13-15V
- Delay time (tv): 0...10 minutes
-
Operation indicators:
- Voltage supply: LED, green
- Relay in working position: LED, yellow
-
Contact:
- Number of changeover: 1
- Contact material: AgNi 0.15
- Max. Switching voltage: 250V
- Max. Switching current: 8A
- Max. Switching power: 2000VA
- Contact life (mech.): 30 x 106
-
Insulation:
- Overvoltage category: 3 (300V)
- Pollution degree: 3 (250V)
- A1/A2->15/16/18: reinforced; 6kV (1.2/50µs)
- Clearance distance >6mm
- Creeping distance: >9mm
-
General data:
- Ambient temperature: -25 ... + 60°C
- Mounting position: any
- Low voltage directive: 2014/35/EU
- EMC Directive: 2014/30/EU
- Connectors: +/- PH2; M3,5; 1,0-1,2Nm
- Wire size : 2 x 0,5 - 2,5mm²
- Mounting Sym. DIN rail En50022
- Dimension L x B x H : (90 x 17,5 x 69,5)mm
- Weight : 77g
- Approvals : CE, RoHs